- CEE-plug collar 16A / phase inverter
- Overload protection
- Short-circuit tripping
- Phase failure impedance
- Connection terminals
- Transparent key cover
- Switching function: 0 - 1
- Actuation type: push buttons ON/OFF
Technical data
| Rated operational voltage Ue: | 400V / 50-60Hz |
| Rated operational current Ie: | 16A |
| Rated breaking capacity AC-3: | 16A / 7,5kW / 400V / 3~ |
| Contacts (main circuit): | closing / 3-pole |
| Overload protection: Setting value: |
thermal, 3-pole, adjustable, automatic reset 10 - 16A |
| Short-circuit trip: Operating current: |
magnetic 14 x In ±20% |
| Switching cylces: | 10E4 |
| Switching frequency: | 25/h |
| Ambient temperature: | -5°C / +40°C |
| Network input: |
CEE-plug collar red 5-pole / Phasenwender CEE 3P+N+E / 6h / 16A / 415V / 50-60Hz |
| Connection PE: N: Motor: |
1 screw terminal 10mm² r 1 screw terminal 10mm² r 3 screw terminals 6mm² r |
| Outgoing: | 2 bottom holes (for wire connection) |
| Degree of protection: | IP 54 |
| Enclosure: | ABS / grey |
| Version: | Built-on / bottom open / buttons top |
| Fixation: | 4 drill holes Ø 6,4mm – 68 x 68mm |
| Dimensions LxWxH: | ca. 230 x 86 x 133mm |
| Weight: | ca. 616g |
| Conformity / Tests: | CE |