- 2 cable glands
- Overload protection
- Short-circuit tripping
- Phase failure impedance
- Connection terminals
- Transparent key cover
- 1 connection wire 200mm (loosely enclosed)
- Switching function: ON / OFF (0 - 1)
- Actuation type: push buttons ON/OFF
Technical data
Rated operational voltage Ue: | 690V AC / 40-60Hz |
Rated operational current Ie: | 2,5A |
Rated breaking capacity AC-3: | 2,5A / 0,37kW / 230V | 1,1kW / 400V | 1,5kW / 690V / 3~ 2,5A / 0,12kW / 120V | 0,25kW / 230V / 1~ |
Contacts (main circuit): | closing / 3-pole |
Actuation: | mechanically ON/OFF, free triggering |
Overload protection: Setting value: |
thermal, 3-pole, adjustable, automatic reset 1,6 - 2,5A |
Short circuit trip: Operating current: |
magnetic 14 x In ±20% |
Switching cycles: | 10E4 |
Switching frequency: | 25/h |
Ambient temperature: | -5°C / +40°C |
Network input: | 1 cable gland M20 (for wire Ø 10 – 14mm) |
Connection: PE: N: Netz: Motor: |
1 screw terminal 10mm² r 1 screw terminal 10mm² r 3 (2) screw terminals 6mm² r 3 (2) screw terminals 6mm² r |
Outgoing: | 1 cable gland M20 (for wire Ø 10 – 14mm) |
Degree of protection: | IP 65 |
Enclosure: | ABS / grey |
Version: | built-on / closed / buttons top |
Fixation: | 4 threaded bushings M5 – 68 x 68mm |
Dimensions LxWxH: | ca. 206 x 86 x 133mm |
Weight: | ca. 547g |
Conformity / Tests: | CE |