- 2 cable glands
- Overload protection
- Short-circuit tripping
- Phase failure impedance
- Connection terminals
- Transparent key cover
- 1 connection wire 200mm (loosely enclosed)
- Switching function: ON / OFF (0 - 1)
- Actuation type: push buttons ON/OFF
Technical data
| Rated operational voltage Ue: | 690V AC / 40-60Hz |
| Rated operational current Ie: | 4A |
| Rated breaking capacity AC-3: | 4A / 0,75kW / 230V | 1,5kW / 400V | 3kW / 690V / 3~ 4A / 0,18kW / 120V | 0,37kW / 230V / 1~ |
| Contacts (main circuit): | closing / 3-pole |
| Actuation: | mechanically ON/OFF, free triggering |
| Overload protection: Setting value: |
thermal, 3-pole, adjustable, automatic reset 2,5 - 4A |
| Short circuit trip: Operating current: |
magnetic 14 x In ±20% |
| Switching cycles: | 10E4 |
| Switching frequency: | 25/h |
| Ambient temperature: | -5°C / +40°C |
| Network input: | 1 cable gland M20 (for wire Ø 10 – 14mm) |
| Connection: PE: N: Netz: Motor: |
1 screw terminal 10mm² r 1 screw terminal 10mm² r 3 (2) screw terminals 6mm² r 3 (2) screw terminals 6mm² r |
| Outgoing: | 1 cable gland M20 (for wire Ø 10 – 14mm) |
| Degree of protection: | IP 65 |
| Enclosure: | ABS / grey |
| Version: | built-on / closed / buttons top |
| Fixation: | 4 threaded bushings M5 – 68 x 68mm |
| Dimensions LxWxH: | ca. 206 x 86 x 133mm |
| Weight: | ca. 545g |
| Conformity / Tests: | CE |